BP Energol Insulating Oil for Electrical Transformers, Switchgear and Circuit Breakers

By Chris Dodds on 17th November, 2015

Follow us on LinkedIn

BP Energol Insulating Oil for Electrical Transformers, Switchgear and Circuit Breakers

 

Electrical Insulating & Transformer Oil

BP Energol JS-A (BS148) Transformer Oil

 

BP Energol JS-A is an electrical insulating oil for transformers, switchgear and circuit breakers. BP Energol oil is a pure mineral hydrocarbon oil specially refined and blended from selected crude oils to comfortably surpass the limiting values of the international specifications IEC 296/1982 (Classes 1 and 2). 


BP Energol JS-A Insulating Oil Features

  • High dielectric strength and low power-loss
  • High oxidation resistance
  • Low sludge formation
  • Excellent cooling properties
  • High purity and high flashpoint

 

BP Energol JS-A Transformer Oil Typical Characteristics
Test Method Value/Unit

Colour

ASTM D1500 <0.5

Density

ISO 3675 / ASTM D92 885 kg/m³

Pour Point

ISO 3016 / ASTM D97 -57°C

Flash Point

ASTM D93 146°C

Kinematic Viscosity 40°C -15°C

ISO 3104 / ASTM D445 11 mm²/s / 400 mm²/s

Neutralisation Value

ASTM D664 0.01 mgKOH/g

Corrosive Sulphur

ASTM D1275 Nil

Anti Oxidant Additive No Breakdown Volt (new dry oil)

IEC 156 >60kV

Dissipation F at 90°C, 50Hz

IEC 156 0.0006

Oxidation Stability IEC74 Neutralisation Value

  0.5 mgKOH/g

Sludge Value

  0.05 %wt

Loss Tangent at 90°C

  0.0006

Gassing Tendency

  +3 mm³/min


 
Energol Performance  : BP Energol JS-A conforms to IEC 296 (1982) Class I, British Standard Specification BS 148 1985 and SABS 555-1985 and carries the mark.

T&D service electrical contractors specialising in the design, build, deployment and management of LV-HV power transformers and distribution transformers.

T&D distribute an extensive range of electrical switchgear and transformer oils for high voltage electrical equipment insulation, 11kV-33kV - this includes Guroflex oils, BICC oils and Trinidite hot pour compounds for filling high voltage switchgear and transformer termination boxes and busbar chambers.

 

  • Further reading :

11kV Cable Box Terminations (Compound Filled) - Breaking Down & Terminating With Triplex Cables

Breaking Down HV Cable Boxes & Using Guroflex - Applications & Tips

 

 

linkedin-logo

Click Here To Join

Invitation

Thorne & Derrick are inviting you to join LinkedIn’s fastest growing Discussion Group : Low & High Voltage Power, Cabling, Jointing, & Hazardous Area Electricals (LV-HV).

Discussion subjects include cable installations, cable jointing, electrical substation, overhead line and electrical construction at LV, 11kV, 33kV and EHV.

Network, engage and promote your profile, company or products with over 10,000 influencers.

Adobe

BP Energol JS-A (BS148) Transformer Oil





Category:  HV Cable Jointing & Terminating

Go back to blog index