home | contact | team t&d | group websites | markets | exports | blog |
![]() |
|
Electrical Insulating & Transformer Oil
BP Energol JS-A (BS148) Transformer Oil
BP Energol JS-A is an electrical insulating oil for transformers, switchgear and circuit breakers. BP Energol oil is a pure mineral hydrocarbon oil specially refined and blended from selected crude oils to comfortably surpass the limiting values of the international specifications IEC 296/1982 (Classes 1 and 2).
BP Energol JS-A Insulating Oil Features
Test | Method | Value/Unit |
Colour |
ASTM D1500 | <0.5 |
Density |
ISO 3675 / ASTM D92 | 885 kg/m³ |
Pour Point |
ISO 3016 / ASTM D97 | -57°C |
Flash Point |
ASTM D93 | 146°C |
Kinematic Viscosity 40°C -15°C |
ISO 3104 / ASTM D445 | 11 mm²/s / 400 mm²/s |
Neutralisation Value |
ASTM D664 | 0.01 mgKOH/g |
Corrosive Sulphur |
ASTM D1275 | Nil |
Anti Oxidant Additive No Breakdown Volt (new dry oil) |
IEC 156 | >60kV |
Dissipation F at 90°C, 50Hz |
IEC 156 | 0.0006 |
Oxidation Stability IEC74 Neutralisation Value |
0.5 mgKOH/g | |
Sludge Value |
0.05 %wt | |
Loss Tangent at 90°C |
0.0006 | |
Gassing Tendency |
+3 mm³/min |
Energol Performance : BP Energol JS-A conforms to IEC 296 (1982) Class I, British Standard Specification BS 148 1985 and SABS 555-1985 and carries the mark.
T&D service electrical contractors specialising in the design, build, deployment and management of LV-HV power transformers and distribution transformers.
T&D distribute an extensive range of electrical switchgear and transformer oils for high voltage electrical equipment insulation, 11kV-33kV - this includes Guroflex oils, BICC oils and Trinidite hot pour compounds for filling high voltage switchgear and transformer termination boxes and busbar chambers.
11kV Cable Box Terminations (Compound Filled) - Breaking Down & Terminating With Triplex Cables
Breaking Down HV Cable Boxes & Using Guroflex - Applications & Tips
Thorne & Derrick are inviting you to join LinkedIn’s fastest growing Discussion Group : Low & High Voltage Power, Cabling, Jointing, & Hazardous Area Electricals (LV-HV).
Discussion subjects include cable installations, cable jointing, electrical substation, overhead line and electrical construction at LV, 11kV, 33kV and EHV.
Network, engage and promote your profile, company or products with over 10,000 influencers.
![]() |
Category: HV Cable Jointing & Terminating