33kV Cable Jointing Video - Single Core 33kV XLPE Heat Shrink Joint

By Chris Dodds on 3rd January, 2013

Follow us on LinkedIn

33kV Cable Jointing Video - Single Core 33kV XLPE Heat Shrink Joint

33kV Cable Jointing Video - Single Core 33kV XLPE Heat Shrink Joint.

Watch Video.

33kV Cable Jointing, Laying & Installation of Heat Shrink Joints - Trench : 33kV single core cables laid direct underground into cable trench to form one three-phase 33kV circuit are generally laid touching in trefoil, bonded together by nylon cable ties. Ducted : 33kV single core cables installed into cable ducts to form a 33kV three-phase circuit should be installed with each core in an individual duct and with the ducts laid touching in trefoil. Cable duct groups should be bound together by cable ties at intervals of one metre - three 33kV single core cables can be installed in a single cable duct for short lengths (eg road crossings). The cable jointer or contractor should check to ensure compliance with regional DNO practice prior to 33kV cable jointing and installation.

Jointing Tools 11kV-33kV Price Offers




Category:  HV Cable Jointing & Terminating