| home | contact | team t&d | group websites | markets | exports | blog |
![]() |
|

CMP Hazardous Area Flameproof ATEX Cable Glands
CMP E1FXATEX Cable Glands
Wire Braided Cables (GSWB)
Zone 1, Zone 2, Zone 21, Zone 22 Cable Glands

CMP E1FX Flameproof (Type ‘d’), Increased Safety (Type ‘e’) and Restricted Breathing (Type ‘nR’) indoor and outdoor cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 hazardous areas with braided, pliable wire armour (PWA), strip Armour and steel tape armour (STA) cable. Deluge Proof cable gland version available, ferrule colour coded "white" for ease of identification.
CMP E1FX cable glands provide a flameproof seal on the cable inner bedding and in addition the gas tight seal has been tested to prove compatibility with Restricted Breathing equipment.
CMP E1FX cable glands are suitable for use with all forms of equipment protection permitted in Zone 1, Zone 2, Zone 21 & Zone 22.
Pictured: CMP E1FX Hazardous Area Cable Gland

CMP Cable Glands E1FX/M - Mining Group Class 1
Flameproof Ex d & Increased Safety Ex e
CMP Type E1FX/M Group 1 Certified Flameproof Exd and Increased Safety Exe cable gland for use in Zone 1
Hazardous Areas with pliable wire armour (PWA) cable providing a cable gland with a flameproof seal on the cable inner sheath and an environmental seal on the cable outer sheath.
Pictured : CMP E1FX/M Cable Gland Mining Group I Flameproof Ex d & Increased Safety Ex
The Mining Group 1 CMP flameproof cable gland being suitable for armoured cables, provides mechanical cable retention and electrical continuity via armour wire termination. A detachable armour cone and CMP AnyWay universal clamping ring arrangement allows the cable to be easily disconnected from the equipment, for maintenance and change out etc, and re-connected with the same consummate ease.
This feature also facilitates remote make off procedures when the cable termination is to be conducted in confined spaces or in areas of restricted access. Separate tightening actions for the inner displacement seal and the armour termination affords maximum control over the pressure applied to the cable inner bedding.
The CMP E1FX/M cable gland is suitable for use with all forms of equipment protection permitted in Zone 1 provided always that the prevailing code of practice, installation and maintenance is observed ie. IEC60079-14.
CMP E1FX Hazardous Area Cable Glands
|
ATEX Code Of Protection Ex II 2G, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da, Ex II 3G Ex nR IIC Gc, IM2 Ex d I Mb, Ex e I Mb |
![]() |
|
IEC Ex Code Of Protection Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb |
![]() |
Pictured: CMP E1FX Cable Gland Installation. Locate the cable gland Armour Cone ensuring the correct side of the cone is outermost - grooved for braid/tape armour and stepped for SWA cables. Pass the cable through the cable gland until the wire armour is engaged with the cone. Spread the wire armour evenly around the cone.

| CMP Cable Gland Size | Thread Entry | Min Thread | Cable Dia Min mm | Cable Dia Max mm | CMP Ref |
| 20S | M20 | 15mm | 9.5 | 15.9 | 20SE1FX1RA |
| 20 | M20 | 15mm | 12.5 | 20.9 | 20E1FX1RA |
| 25S | M25 | 15mm | 14.0 | 22.0 | 25SE1FX1RA |
| 25 | M25 | 15mm | 18.2 | 26.2 | 25E1FX1RA |
| 32 | M32 | 15mm | 23.7 | 33.9 | 32E1FX1RA |
| 40 | M40 | 15mm | 27.9 | 40.4 | 40E1FX1RA |
| 50S | M50 | 15mm | 35.2 | 46.7 | 50SE1FX1RA |
| 50 | M50 | 15mm | 40.4 | 53.1 | 50E1FX1RA |
| 63S | M63 | 15mm | 45.6 | 59.4 | 63SE1FX1RA |
| 63 | M63 | 15mm | 54.6 | 65.9 | 63E1FX1RA |
| 75S | M75 | 15mm | 59.0 | 72.1 | 75SE1FX1RA |
| 75 | M75 | 15mm | 66.7 | 78.5 | 75E1FX1RA |
| 90 | M90 | 24mm | 76.2 | 90.4 | 90E1FX1RA |
| 100 | M100 | 24mm | 86.1 | 101.5 | 100E1FX1RA |
| 115 | M115 | 24mm | 101.5 | 110.3 | 115E1FX1RA |
| 130 | M130 | 24mm | 114.2 | 123.3 | 130E1FX1RA |
Video: CMP Products - E1FX Cable Gland - Remote Make Off
CMP E1FX Cable Glands - Installation Instruction
CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables