Prysmian Draka BFOU 0,6/1kV P5/P12 Power Cable has fixed installation for power, control and lighting in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists.

The BFOU 0,6/1kV P5/P12 power cable is used for installation in areas exposed to MUD and drilling/cleaning fluids. Prysmian Draka BFOU 0,6/1kV P5/P12 power cable meets the MUD resistance requirement in NEK 606.Prysmian Draka Cables - FlexFlame BFOU 0,6/1kV P5/P12 Power (Double Braided) Cable Application

 

Prysmian Draka Cables - FlexFlame BFOU 0,6/1kV P5/P12 Power (Double Braided) Cable Approvals

  • IEC 60092-353 - Design
  • IEC 60228 class 2 - Conductor
  • IEC 60092-351 - Insulation
  • IEC 60092-359 - Sheath
  • IEC 60332-1 - Flame Retardant
  • IEC 60332-3-22 - Flame Retardant
  • IEC 60331-21 - Fire Resistant
  • IEC 60754-1,2 - Halogen Free
  • IEC 61034-1,2 - Low Smoke

T&D distribute Prysmian Draka marine and offshore cables with Lloyds Register, DNV GL and NEK 606 standards. 

Prysmian

Prysmian Draka Cables - FlexFlame BFOU 0,6/1kV P5/P12 Power (Double Braided) Cable Construction

  1. Conductor - Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
  2. Insulation - B Mica-tape + EP-rubber, IEC 60092-351 (EPR)
  3. Lay up / Shielding Cores - laid up in concentric layers
  4. Inner Covering - Flame retardant and halogen-free thermoplastic compound
  5. Tape Over Inner Covering - PET tape + rubberized Polyamide tape
  6. Armour/screen - Two layers of tinned copper wire braid (double braid)
  7. Tape Over Armour/Screen - PET tape + rubberized Polyamide tape
  8. Outer Sheath - Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359)
  9. Marking Text - E.g. "meter" "år" DRAKA 01 BFOU 0,6/1kV P5/P12 3 x 25/16 mm2 FLEX - FLAME IEC 60331-21 IEC 60332-3-22 ETL Classified No. 3067229
  10. Manufacturing Unit - DRAKA 01 = Draka Norsk Kabel