Prysmian Draka BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument
HydroCarbon Fire Resistant, Flame Retardant Halogen-Free Instrumentation
BFOU-HCF(c) 250V MGT/EPR/EPR/TCWB/EVA/HCF/SHF1
NEK 606 Code S16
Prysmian Draka Offshore Drilling Cables
Prysmian Draka Cables - BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument Cable Application
Prysmian Draka BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument cable has fixed installation for instrumentation, communication, control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for hydrocarbon fire resistance is vital.
Prysmian Draka Cables - BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument Cable Approvals
- IEC 60092-376 (2003-05) - Design
- Draka Norsk Kabel - HCF protection
- IEC 60228 class 2 - Conductor
- IEC 60092-351 - Insulation
- IEC 60092-359 - Sheath
- IEC 60332-1 - Flame Retardant
- IEC 60332-3-22 - Flame Retardant
- IEC 60331-21 - Fire Resistant
- UL 1709 / ASTM E1529 - HC Fire resistance
- IEC 600754-1,2 - Halogen Free
- IEC 61034-1,2 - Low Smoke
T&D distribute Prysmian Draka marine and offshore cables with Lloyds Register, DNV GL and NEK 606 standards.

Prysmian Draka Cables - BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument Cable Construction
- Conductor - Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
- Insulation - B Mica-tape + EP-rubber, IEC 60092-351 (EPR)
- Pair / Triple /Quad Twisting - Colour coded cores twisted together. Pairs/Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair/triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triples. Pairs/triples are identified by numbered tape or by numbers printed directly on the insulated conductors
- Lay up /Shielding - Individually shielded pairs/triples/quads are laid up in concentric layers and wrapped with a PETP tape
- Inner Covering - Flame retardant and halogen-free thermoplastic compound
- Tape Over Inner Covering - PET tape
- Armour/Screen - Tinned copper wire braid
- Tape Over Armour/Screen - PET tape
- Outer Sheath - Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359)
- HCF Protection -HCF Extruded heatblock compound
- Tape - Lapped Glassfibre tape
- Overall Sheath Flame retardant, halogen-free thermoplastic compound, SHF1 (IEC 60092-359)