Prysmian Draka Cables - BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument Cable

Prysmian Draka Cables - BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument Cable

Prysmian Draka BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument 

HydroCarbon Fire Resistant, Flame Retardant Halogen-Free Instrumentation

BFOU-HCF(c) 250V MGT/EPR/EPR/TCWB/EVA/HCF/SHF1

NEK 606 Code S16

Prysmian Draka Offshore Drilling Cables

 

Prysmian Draka Cables - BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument Cable Application

Prysmian Draka BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument cable has fixed installation for instrumentation, communication, control and alarm systems in both EX- and safe areas, emergency and critical systems where requirement for hydrocarbon fire resistance is vital.Prysmian Draka Cables - BFOU-HCF(c) 250V S16 / 1100C / 30 minutes Instrument Cable Application

 

 

Prysmian Draka Cables - BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument Cable Approvals

  • IEC 60092-376 (2003-05) - Design
  • Draka Norsk Kabel - HCF protection
  • IEC 60228 class 2 - Conductor
  • IEC 60092-351 - Insulation
  • IEC 60092-359 - Sheath
  • IEC 60332-1 - Flame Retardant
  • IEC 60332-3-22 - Flame Retardant
  • IEC 60331-21 - Fire Resistant
  • UL 1709 / ASTM E1529 - HC Fire resistance
  • IEC 600754-1,2 - Halogen Free
  • IEC 61034-1,2 - Low Smoke

T&D distribute Prysmian Draka marine and offshore cables with Lloyds Register, DNV GL and NEK 606 standards. 

Prysmian

Prysmian Draka Cables - BFOU-HCF(c) 250V S16 / 1100°C / 30 minutes Instrument Cable Construction

  1. Conductor - Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
  2. Insulation - B Mica-tape + EP-rubber, IEC 60092-351 (EPR)
  3. Pair / Triple /Quad Twisting -  Colour coded cores twisted together. Pairs/Triples are screened by copper backed polyester tape with tinned copper drain wire. Each pair/triple is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triples. Pairs/triples are identified by numbered tape or by numbers printed directly on the insulated conductors
  4. Lay up /Shielding - Individually shielded pairs/triples/quads are laid up in concentric layers and wrapped with a PETP tape
  5. Inner Covering - Flame retardant and halogen-free thermoplastic compound
  6. Tape Over Inner Covering - PET tape
  7. Armour/Screen - Tinned copper wire braid
  8. Tape Over Armour/Screen - PET tape
  9. Outer Sheath - Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359)
  10. HCF Protection -HCF Extruded heatblock compound
  11. Tape - Lapped Glassfibre tape
  12. Overall Sheath Flame retardant, halogen-free thermoplastic compound, SHF1 (IEC 60092-359)

T&D supply the complete range of Prysmian cable glands, cable cleats and cable joints suitable for industrial and hazardous area LV, MV & HV cable installations - this includes FP Fire Resistant cables.

Prysmian Cable Joints Glands Cleats