Prysmian Draka Cables BFOU 0,6/1kV P5/P12 Power Cable

Prysmian Draka Cables  BFOU 0,6/1kV P5/P12 Power Cable

Prysmian Draka Cables – BFOU 0,6/1kV P5/P12 Power Cable

Fire Resistant, Flame Retardant Halogen-Free Power Cable 

Mud resistant BFOU 0,6/1kV MGT/EPR/EPR/TCWB/EVA

NEK 606 CodeP5/P12

Prysmian Draka Offshore Drilling Cables 

 

 

Prysmian Draka Cables – BFOU 0,6/1kV P5/P12 Power Cable Application

Prysmian Draka BFOU 0,6/1kV P5/P12 Power Cable has fixed installation for power, control and lighting in both EX- and safe areas, emergency and critical systems where requirement for fire resistance exists.

The BFOU 0,6/1kV P5/P12 power cable is used for installation in areas exposed to MUD and drilling/cleaning fluids. Prysmian Draka BFOU 0,6/1kV P5/P12 power cable meets the MUD resistance requirement in NEK 606.Prysmian Draka Cables  BFOU 0,6/1kV P5/P12 Power Cable Application

 

Prysmian Draka Cables – BFOU 0,6/1kV P5/P12 Power Cable Approvals

  • IEC 60092-353 - Design
  • IEC 60228 class 2 - Conductor
  • IEC 60092-351 - Insulation
  • IEC 60092-359 - Sheath
  • IEC 60332-1 - Flame Retardant
  • IEC 60332-3-22 - Flame Retardant
  • IEC 60331-21 - Fire Resistant
  • IEC 60754-1,2 - Halogen Free
  • IEC 61034-1,2 - Low Smoke

T&D distribute Prysmian Draka marine and offshore cables with Lloyds Register, DNV GL and NEK 606 standards. 

Prysmian

Prysmian Draka Cables – BFOU 0,6/1kV P5/P12 Power Cable Construction

  1. Conductor - Tinned annealed stranded circular copper (STCC), IEC 60228 class 2
  2. Insulation - B Mica-tape + EP-rubber, IEC 60092-351 (EPR)
  3. Lay up / Shielding - Cores laid up in concentric layers
  4. Inner Covering - F Flame retardant and halogen-free thermoplastic compound
  5. Tape Over Inner Covering - PET tape
  6. Armour/Screen - O Tinned annealed copper wire braid
  7. Tape Over Armour/Screen - PET tape
  8. Outer Sheath - U Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359)
  9. Marking Text - E.g. "meter" "år" DRAKA 01 BFOU 0,6/1kV P5/P12 3 x 25/16 mm2 FLEX -FLAME IEC 60331-21 IEC 60332-3-22 ETL Classified No. 3067229
  10. Manufacturing Unit - DRAKA 01 = Draka Norsk Kabel
  11. Outer Sheath Colour - Black

T&D supply the complete range of Prysmian cable glands, cable cleats and cable joints suitable for industrial and hazardous area LV, MV & HV cable installations - this includes FP Fire Resistant cables.

Prysmian Cable Joints Glands Cleats

UK Time - GMT: