Marechal DS9 Plugs, Sockets (Decontactors) 150Amps

Marechal DS Industrial Plugs & Sockets

Marechal DS Plugs & Sockets

Industrial Power Supply & Motor Connections

Marechal Plugs & Sockets - Decontactors

 

Marechal DS9 150Amp Plug & Socket (Decontactors) for Low Voltage Industrial Power Supply and Motor Connections

Marechal DS range of industrial power supply and motor connection plugs and sockets provide low voltage distribution, 30amps-250amps.

Marechal DS range industrial plugs are the quality standard for manufacturing industry providing benefits compliant with International Standard IEC60309-1 and European Standard EN60309-1 (Plugs & Sockets Outlets for Industrial Purposes).

Marechal DS9 Decontactor Plugs & Sockets Specifications:

  • Rated current (with wiring according to standard): 150A
  • Maximum Voltage: 1000V
  • IP Protection Lid Closed: IP55 (GRP version: IP66/IP67)
  • IP Protection Connected Plug: IP54 (GRP version: IP66/IP67)
  • Load Breaking Capability: AC-22 / AC-23
  • GRP Casings
  • Shock Resistance: IK08
  • Ambient Temperature: -40°C to +60°C 
  • Equipped with silver-nickel butt contacts for lifetime reliability

Marechal DS9 Plugs, Sockets (Decontactors) 150Amps

Rated Current (with wiring according to standard) Marechal DS9 GRP Marechal DS9 Metal
50A 50A
Maximum Voltage 1000V 1000V
IP Protection Lid Closed IP66/IP67 IP55
IP Protection Connected Plug IP66/IP67 IP54
Shock Resistance IK08 IK09
Ambient Temperature -40ºC to +60ºC -40ºC to +60ºC
Flexible Wiring (Min-Max) 25mm² - 70mm² 25mm² - 70mm²
Stranded Wiring (Min-Max) 25mm² - 95mm² 25mm² - 95mm²
Other Wiring On Request On Request
Keying Positions 24 24

Marechal DS9 Plugs - Load Break Capability

  • Comply with IEC EN 60309-1 and IEC EN 60309-4 standards  - (150 A / 500 V) or (125 A / 690 A)
  • Load-break capability according to IEC EN 60947-3 / AC-22A - (90 A / 690 V) or (150 A / 400 V)
  • Load-break capability according to IEC EN 60947-3 / AC-23A - 100 A / 440 V
  • Short-circuit current Icc - 10 kA

Marechal DS3 Plugs 30A 690V Decontactors (AC22 AC23 IEC60309)  

The DS9 is available in a wide range of voltages and polarity options for both female socket outlets and male inlet plugs:

  • 190-230V, 3P+E
  • 220-250V, 1P+N+E
  • 380V-440V, 3P+E
  • 220-250V & 380V-440V (Dual Voltage), 3P+N+E
  • 660-690V, 3P+E
  • 380V-440V & 660V-690V (Dual Voltage), 3P+N+E
  • 1000V, 3P+E

Marechal DS Plugs 30A-250A Decontactors - Technical Features

Marechal Part Number Marechal DS1 Marechal DS3 Marechal DS6 Marechal DS9 Marechal DS2
Rated Current (ln) 30 Amp Plug 50 Amp Plug 90 Amp Plug 150 Amp Plug 250 Amp Plug
Umax 690 V 1000 V 1000 V 1000 V 1000 V
AC-22 Switching Capacity 16 A / 690 V 32 A / 690 V 63 A / 690 V 150 A / 400 V 250 A / 400 V
AC-23 Switching Capacity 30 A / 400 V 50 A / 400 V 90 A / 400 V 100 A / 440 V 160 A / 440 V
Auxiliary Contacts (Optional) 2 4 4 6 7
Keying Positions (To distinguish between different power supplies & applications) 24 24 24 24 12
Ambient Temperature -40 °C to +60 °C for all DS
Short Circuit Current lcc 10 kA for all DS

 

Marechal DS9 - Socket Outlets & Inlets

Voltage 50Hz Polarity Marechal Socket Outlet (Female) DS9 150A Marechal Inlet (Male) DS9 150A
190-230V 3P+E 3194033 3198033
220-250V 1P+N+E 3194015 3198015
380-440V 3P+E 3194013 3198013
220-250V / 380-440V 3P+N+E 3194017 3198017
660-690V 3P+E 3194193 3198193
380-440V /  660-690V 3P+N+E 3194197 3198197
1000V 3P+E 3194223 3198223

YouTube Video Playlist: Marechal Industrial Plugs & Sockets

 

T&D also distribute hazardous area isolatorscontrol panels and distribution boards, electrical enclosures and motor starters certified according to ATEX for use in Zone 1 & Zone 2 (gas/vapour) explosive atmospheres.

Hazardous Area ATEX Zone 1 Zone 2 - Power Distribution

 

Adobe Marechal Decontactors - Plug & Socket + Switch

Adobe Marechal DS9 Plugs, Sockets (Decontactors) 150Amps

UK Time - GMT:

Marechal DS9 Plugs, Sockets (Decontactors) 150Amps