CMP E2FW Hazardous Area Flameproof ATEX Cable Glands for Lead Sheathed Cables

CMP Cable Glands

CMP E2FW Cable GlandsCMP Hazardous Area Flameproof ATEX Cable Glands

CMP E2FW ATEX Cable Glands

 Lead Sheathed Cables

Zone 1, Zone 2, Zone 21, Zone 22 Cable Glands

 

CMP Hazardous Area Cable Glands

CMP E2FW Flameproof (Type ‘d’), Increased Safety (Type ‘e’) and Restricted Breathing (Type ‘nR’) cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 hazardous areas.

CMP E2FW cable glands are for use with lead covered, lead sheathed and single wire armour (SWA) cable.

CMP E2FW cable glands provide a flameproof seal on the cable inner lead covering and in addition the gas tight seal has been tested to prove compatibility with Restricted Breathing equipment. 

CMP E2FW cable glands allow mechanical cable retention and earth continuity via the cable armour termination and also earth bonding of the inner lead covering or lead sheath.

CMP E2FW cable glands are suitable for use with all forms of equipment protection permitted in Zone 1, Zone 2, Zone 21 & Zone 22.

 

Pictured: CMP E2FW Hazardous Area Cable Glands

CMP E2FW Hazardous Area Cable Glands

 

CMP E2FW Cable Gland Specification - CMP Type E2FW Tri-Star Triple Certified Flameproof (Type ‘d’), Increased Safety (Type ‘e’) and Restricted Breathing (Type ‘nR’) cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 Hazardous Areas with lead covered or lead sheathed and single wire armour (SWA) cable.

CMP E2FW cable gland provides a flameproof seal on the cable inner lead covering and in addition the gas tight seal has been tested to prove compatibility with Restricted Breathing equipment that relies upon flammable gases being excluded from the main enclosure. 

CMP E2FW cable gland allows mechanical cable retention and earth continuity via the cable armour termination and also earth bonding of the inner lead covering or lead sheath. Separate tightening actions for the inner displacement seal and the armour termination afford maximum control over the pressure applied to the cable inner lead covering, and also allows the effectiveness of the gas tight seal to be tested.

A detachable armour cone and AnyWay clamping ring arrangement facilitates remote make off and enables the cable to be disconnected from the equipment. An environmental / load retention seal is provided on the cable outer sheath. The CMP E2FW Tri-Star Cable Gland is suitable for use with all forms of equipment protection permitted in Zone 1, Zone 2, Zone 21 & Zone 22 provided always that the prevailing code of practice for selection and installation is observed, e.g. IEC 60079-14

 

Pictured : CMP E2FW Cable Gland - Assembly Kit List

CMP E2FW Cable Glands

 

CMP E2FW Hazardous Area Cable Glands

  • Cable Gland Type: CMP E2FW
  • Cable Gland Material: Brass, Electroless Nickel Plated Brass, Aluminium
  • Cable Type: Lead Sheathed and Single Wire Armour (AWA)
  • Ingress Protection: IP66 (Standard), IP67 & IP68
  • ATEX Certificate: SIRA13ATEX1071X, SIRA13ATEX4077X
  • IEC Ex Certificate: IECEx SIR 13.0026X

 

ATEX Code Of Protection

Ex II 2G, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da, Ex II 3G Ex nR IIC Gc, IM2 Ex d I Mb, Ex e I Mb

ATEX 

IEC Ex Code Of Protection

Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb

IEC Ex

Adobe CMP E2FW Hazardous Area Flameproof ATEX Cable Glands for Lead Sheathed Cables

Adobe CMP E2FW Cable Glands - Installation Instruction