CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables (GSWB)

CMP Cable Glands

ATEX CertifiedCMP Hazardous Area Flameproof ATEX Cable Glands

CMP E1FXATEX Cable Glands

 Wire Braided Cables (GSWB)

Zone 1, Zone 2, Zone 21, Zone 22 Cable Glands

CMP Hazardous Area Cable Glands

CMP E1FX Flameproof (Type ‘d’), Increased Safety (Type ‘e’) and Restricted Breathing (Type ‘nR’) indoor and outdoor cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 hazardous areas with braided, pliable wire armour (PWA), strip Armour and steel tape armour (STA) cable. Deluge Proof cable gland version available, ferrule colour coded "white" for ease of identification.

CMP E1FX cable glands provide a flameproof seal on the cable inner bedding and in addition the gas tight seal has been tested to prove compatibility with Restricted Breathing equipment. 

CMP E1FX cable glands are suitable for use with all forms of equipment protection permitted in Zone 1, Zone 2, Zone 21 & Zone 22.

 

Pictured: CMP E1FX Hazardous Area Cable Gland

CMP E1FX Hazardous Area Cable Glands

 

CMP Cable Glands E1FX/M - Mining Group Class 1

Flameproof Ex d & Increased Safety Ex e 

CMP Type E1FX/M Group 1 Certified Flameproof Exd and Increased Safety Exe cable gland for use in Zone 1CMP Group 1 Mining Cable Glands Hazardous Areas with pliable wire armour (PWA) cable providing a cable gland with a flameproof seal on the cable inner sheath and an environmental seal on the cable outer sheath.

Pictured : CMP E1FX/M Cable Gland Mining Group I Flameproof Ex d & Increased Safety Ex

The Mining Group 1 CMP flameproof cable gland being suitable for armoured cables, provides mechanical cable retention and electrical continuity via armour wire termination. A detachable armour cone and CMP AnyWay universal clamping ring arrangement allows the cable to be easily disconnected from the equipment, for maintenance and change out etc, and re-connected with the same consummate ease.

This feature also facilitates remote make off procedures when the cable termination is to be conducted in confined spaces or in areas of restricted access. Separate tightening actions for the inner displacement seal and the armour termination affords maximum control over the pressure applied to the cable inner bedding.

The CMP E1FX/M cable gland is suitable for use with all forms of equipment protection permitted in Zone 1 provided always that the prevailing code of practice, installation and maintenance is observed ie. IEC60079-14.

 

CMP E1FX Hazardous Area Cable Glands

  • Cable Gland Type: CMP E1FX
  • Cable Gland Material: Brass, Nickel Plated Brass, Aluminium
  • Cable Type: Screened Flexible Wire Braid (e.g. CY / SY), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Wire Braid Armour (e.g. SWB), Aluminium Strip Armour (ASA), Armoured & Jacketed
  • Ingress Protection: IP66 (Standard), IP67 & IP68 option available on request
  • ATEX Certificate: SIRA13ATEX1071X, SIRA13ATEX4077X
  • IEC Ex Certificate: IECEx SIR 13.0026X

ATEX Code Of Protection

Ex II 2G, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da, Ex II 3G Ex nR IIC Gc, IM2 Ex d I Mb, Ex e I Mb

ATEX

IEC Ex Code Of Protection 

Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb

IEC Ex

 

Pictured: CMP E1FX Cable Gland Installation. Locate the cable gland Armour Cone ensuring the correct side of the cone is outermost - grooved for braid/tape armour and stepped for SWA cables. Pass the cable through the cable gland until the wire armour is engaged with the cone. Spread the wire armour evenly around the cone.

INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND TYPES E

 

CMP E1FX Tri-Star ATEX Hazardous Area Cable Glands
CMP Cable Gland Size Thread Entry Min Thread  Cable Dia Min  mm Cable Dia Max mm CMP Ref
20S M20 15mm 9.5 15.9 20SE1FX1RA
20 M20 15mm 12.5 20.9 20E1FX1RA
25S M25 15mm 14.0 22.0 25SE1FX1RA
25 M25 15mm 18.2 26.2 25E1FX1RA
32 M32 15mm 23.7 33.9 32E1FX1RA
40 M40 15mm 27.9 40.4 40E1FX1RA
50S M50 15mm 35.2 46.7 50SE1FX1RA
50 M50 15mm 40.4 53.1 50E1FX1RA
63S M63 15mm 45.6 59.4 63SE1FX1RA
63 M63 15mm 54.6 65.9 63E1FX1RA
75S M75 15mm 59.0 72.1 75SE1FX1RA
75 M75 15mm 66.7 78.5 75E1FX1RA
90 M90 24mm 76.2 90.4 90E1FX1RA
100 M100 24mm 86.1 101.5 100E1FX1RA
115 M115 24mm 101.5 110.3 115E1FX1RA
130 M130 24mm 114.2 123.3 130E1FX1RA

Video: CMP Products - E1FX Cable Gland - Remote Make Off

Adobe CMP E1FX Cable Glands - Installation Instruction

Adobe CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables

UK Time - GMT: