Prysmian Draka Cables - BFOU-HCF 0,6/1kV P34/1100°C/30-60 minutes Instrument Cable

Prysmian Draka Cables - BFOU-HCF 0,6/1kV P34/1100°C/30-60 minutes Instrument Cable

Prysmian Draka BFOU-HCF 0,6/1kV P34/1100°C/30-60 minutes Instrument

HydroCarbon Fire Resistant, Flame Retardant Halogen-Free Instrumentation

BFOU-HCF 0,6/1kV MGT/EPR/EPR/TCWB/EVA/HCF/SHF1

NEK 606 Code P34

Prysmian Draka Offshore Drilling Cables

 

Prysmian Draka Cables - BFOU-HCF 0,6/1kV P34/1100°C/30-60 minutes Instrument Cable Application

Prysmian Draka BFOU-HCF 0,6/1kV P34/1100°C/30-60 minutes Instrument cable has fixed installation for power, control and lightning in both EX- and safe areas, emergency and critical systems where requirement for fire resistance is vital.Prysmian Draka Cables - BFOU-HCF 0,6/1kV P34/1100C/30-60 minutes Instrument Cable Application

 

Prysmian Draka Cables - BFOU-HCF 0,6/1kV P34/1100°C/30-60 minutes Instrument Cable Approvals

  • IEC 60092-353 - Design
  • Draka Norsk Kabel - HCF protection
  • IEC 60228 class 2 - Conductor
  • IEC 60092-351 - Insulation
  • IEC 60092-359 - Sheath
  • IEC 60332-1 - Flame Retardant
  • IEC 60332-3-22 - Flame Retardant
  • IEC 60331-21 - Fire Resistant
  • UL 1709 / ASTM E1529 - HC Fire resistance
  • IEC 600754-1,2 - Halogen Free
  • IEC 61034-1,2 - Low Smoke

T&D distribute Prysmian Draka marine and offshore cables with Lloyds Register, DNV GL and NEK 606 standards. 

Prysmian

Prysmian Draka Cables - BFOU-HCF 0,6/1kV P34/1100°C/30-60 minutes Instrument Cable Construction

  • Conductor - Tinned stranded circular copper, IEC 60228 class 2
  • Insulation - B Mica-tape + EP-rubber, IEC 60092-351 (EPR)
  • Lay up / Shielding - Cores laid up in concentric layers
  • Inner Covering - Flame retardant and halogen-free thermoplastic compound
  • Tape Over Bedding - PET tape
  • Armour/Screen - Tinned copper wire braid
  • Tape Over Armour/Screen - PET tape
  • Outer Sheath - Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-359)
  • HCF Protection -HCF Extruded heatblock compound
  • Tape - Lapped glassfibre tape
  • Overall Sheath - Flame retardant, halogen-free thermoplastic compound, SHF1 (IEC 60092-359)
  • Marking Text - Eg. "meter" "år" DRAKA NORSK KABEL BFOU-HCF 0,6/1kV P34 12 x 2,5/10 mm2 HCF 1100/30 FLEX - FLAME IEC 60331-21 IEC 60332-3-22
  • Outer Sheath Colour - Black

T&D supply the complete range of Prysmian cable glands, cable cleats and cable joints suitable for industrial and hazardous area LV, MV & HV cable installations - this includes FP Fire Resistant cables.