Cable Heating Blankets for Straightening High Voltage HV Cables Prior To Jointing - Hemi Heating AB

By Chris Dodds on 28th August, 2015

Follow us on LinkedIn

Cable Heating Blankets for Straightening High Voltage HV Cables Prior To Jointing - Hemi Heating AB

Cable Heating Blankets For Straightening High Voltage Cables.

 

HV 66kV 132kV 275kV 400kV

Hemi Heating AB have developed a standard range of cable heating jackets for straightening and relaxation of high voltage cables. Cable heating jackets are used to straighten extra high voltage and high voltage (EHV-HV) power and submarine cables in the power utility and renewable energy sectors.

Cable heating blankets enable the straightening of HV cable prior to jointing and terminating by the cable jointers - typically the cable blanket would enable the heating of 132kV-400kV cable prior to the installation of Tyco, ABB Kabeldon, Pfisterer or Prysmian cable joints.

Cable heating jackets are delivered together with a control box containing an PID-temperature control with dual LED display showing setpoint and actual temperature.

HV Cable Blankets - Hemi Heating AB Heating Jackets

Hemi Heating AB Cable Heating Jacket Benefits:

  • Quick installation
  • Homogenous temperature 
  • Robust design 

Pictured : Cable Heating Jackets For HV High Voltage Cables

Cable Heating Blankets

Hemi Heating AB Cable Heating Jacket Technical Data

  • Operating voltage: 220-240VAC
  • Cable range (mm): Ø70-190
  • Normal heating temperature: 95°C (adjustable setpoint, PID control)
  • Built in over temperature switch: 110°C
  • Insulation thickness: 25mm
  • Cables: 5m power inlet, 5m to heater jacket
  • RCD: 30mA, Type A
  • IP rating: IP44 

Hemi Cable Heating AB Item 

Cable Diameter 

Blanket Length 

CSR 70-115/1 Cable Blanket

70mm-115mm

1500mm

CSR 70-115/2 Cable Blanket 

70mm-115mm

1500mm

CSR EP 25 

Extension Piece 25mm

1500mm

CSR SP2000 

Straightening Al-profile

2000mm

132kV Cable Jointing - High Voltage Cables

Pictured : 132kV Cable After Heating & Straightening. Here the HV cable jointer has heated the 132kV offshore cable with the lead on, then straightened the cable in an aluminium angle with ratchet straps.

Image : Simon Chapman (Balfour Beatty).

132kV Cable Heating

EHV cable heating jackets are also suitable for straightening 64/110kV and 127/220kV XLPE insulated transmission and distribution cables with Milliken segmental conductors. 

Pictured: 155kv NKT GIS Termination

Image: Richie Rice EHV Cable Jointer

155kv NKT GIS Termination.

 