home | contact | team t&d | group websites | markets | exports | blog |
|
11kV XLPE AWA Single Core 400sqmm Copper Cable - BS6622 BS7835
Minimum average thickness of insulation : 3.4mm
Nominal diameter of primary insulation : 32.3mm
Nominal thickness of PVC/LSOH bedding : 1.2mm
Nominal thickness of PVC/LSOH oversheath : 2.4mm
Nominal overall diameter of cable mm : 45.2mm
Nominal internal diameter of cable ducts : 100mm
Minimum bending radius : 700mm
Cable laid in ground : 270 amps current rating
Cable pulled/drawn into ducts : 260 amps current rating
Cable laid in air : 310 amps current rating
T&D distribute an extensive range of cable joints, cable terminations (heat shrink and cold shrink), cable duct seals, cable cleats, cable glands, cable ties and cable pulling equipment for use with high voltage 11kV power cables.
11kV XLPE AWA Single Core 400sqmm Copper Cable
Prysmian Cable Joints, Glands, Cleats, Terminations - Catalogue