Prysmian FP400 Fire Resistant Power Cable – BS6387 CWZ Armoured Cables
Fire Resistant Cable
Prysmian FP400
Prysmian FP400 is a tough, armoured fire resistant cable with low fire hazard properties and limited fire resistance making it ideal for part of the power or control circuits in buildings if circuit integrity in the event of fire is required.
FP400 cable maintains circuit integrity during BS6387 CWZ fire test and produces very low levels of smoke and virtually no acidic gases.
FP400 handles like a standard armoured cable and can be installed just as easily without special tools or accessories and it is suitable for indoor or outdoor use with installation either directly buried or in a trough, fixed direct, tray or ladder.
Prysmian FP400 Fire Resistant Cable
Features & Benefits
- Plain annealed copper stranded (class 2) conductor to meet the requirements of BS EN 60228 class 2
- Mineral ceramic (Mica/Glass) fire resistant tape. 90°C cross-linked insulation
- Extruded LS0H bedding and sheath with single layer of galvanised steel wire armour
- FP400 cable is available in brown-black, brown-black-grey and blue-brown-black-grey as standard. Available to special order in red-black, red-yellow-blue or black-red-yellow-blue on request. 7-37 cores in white with printed numbers
- Temperature range -25 to +90ºC
- Bending radius 8D
- High mechanical impact protection
- Fire performance BS EN 60332-1-2, BS EN 60332-3-24
- Halogen free fire resistant cables – BS EN 60754-1
- Low smoke emissions – BS EN 61034-2
- Fire resistant BS 6387 CWZ
Prysmian FP400 Fire Resistant Cable
Performance Standards
- 600/1000V
- BS6387 CWZ
- BS7846 F2
- BASEC Approved
- LPCB Approved
- London Underground approved LU 1-085A (Previously ‘Section 12’)
- Low fire hazard cable with low smoke, zero halogen and flame retardant
- Manufactured in UK
Prysmian FP400 Fire Resistant Cable – Single Core Cables
Nominal Cross Sectional Area (sqmm) | Approximate Overall Diameter (mm) | Approximate Diameter Under Armour (mm) | Nominal Diameter of Armour Wires (mm) | Approximate Cable Weight (kg/km) | Maximum Conductor Resistance at 20ºC (Ω/km) | Short Circuit Rating (1 second) Amps | Current Rating DC or Single Phase AC Clipped Direct (Amps) | Current Rating Three Phase DC Free Air (Amps) | Volt Drop Three Phase AC (mV/A/m) |
Three Core | |||||||||
1.5 | 13.5 | 9.2 | 0.9 | 350 | 12.1 | 0.20 | 23 | 25 | 27 |
2.5 | 15.0 | 10.5 | 0.9 | 430 | 7.41 | 0.35 | 31 | 33 | 16 |
4 | 16.0 | 11.5 | 0.9 | 510 | 4.61 | 0.57 | 42 | 44 | 10 |
6 | 17.5 | 12.9 | 0.9 | 620 | 3.08 | 0.86 | 53 | 56 | 6.8 |
10 | 21.0 | 15.2 | 1.25 | 950 | 1.83 | 1.4 | 73 | 78 | 4.0 |
16 | 23.0 | 16.7 | 1.25 | 1200 | 1.15 | 2.2 | 94 | 99 | 2.5 |
25 | 27.0 | 20.4 | 1.6 | 1800 | 0.727 | 3.6 | 124 | 131 | 1.65 |
35 | 30.0 | 23.2 | 1.6 | 2200 | 0.524 | 5.0 | 154 | 162 | 1.15 |
50 | 31.0 | 23.8 | 1.6 | 2500 | 0.387 | 7.1 | 187 | 197 | 0.87 |
70 | 34.0 | 27.0 | 1.6 | 3200 | 0.268 | 10.0 | 238 | 251 | 0.60 |
95 | 38.0 | 30.0 | 2.0 | 4300 | 0.193 | 13.6 | 289 | 304 | 0.45 |
120 | 41.0 | 33.1 | 2.0 | 5200 | 0.153 | 17.2 | 335 | 353 | 0.37 |
150 | 46.0 | 37.0 | 2.5 | 6500 | 0.124 | 21.4 | 386 | 406 | 0.30 |
185 | 51.0 | 41.4 | 2.5 | 7900 | 0.0991 | 26.5 | 441 | 463 | 0.26 |
240 | 56.0 | 46.1 | 2.5 | 9900 | 0.0754 | 34.3 | 520 | 546 | 0.21 |
300 | 61.0 | 50.6 | 2.5 | 11900 | 0.0601 | 42.9 | 599 | 628 | 0.185 |
400 | 67.0 | 56.3 | 2.5 | 14600 | 0.0470 | 57.2 | 673 | 728 | 0.165 |
Four Core | |||||||||
1.5 | 14.5 | 10.2 | 0.9 | 395 | 12.1 | 0.20 | 23 | 25 | 27 |
2.5 | 16.5 | 11.7 | 0.9 | 430 | 7.41 | 0.35 | 31 | 33 | 16 |
4 | 17.5 | 12.9 | 0.9 | 510 | 4.61 | 0.57 | 42 | 44 | 10 |
6 | 20.0 | 14.4 | 0.9 | 840 | 3.08 | 0.86 | 53 | 56 | 6.8 |
10 | 22.0 | 16.8 | 1.25 | 1100 | 1.83 | 1.4 | 73 | 78 | 4.0 |
16 | 24.0 | 18.4 | 1.25 | 1400 | 1.15 | 2.2 | 94 | 99 | 2.5 |
25 | 30.0 | 22.6 | 1.6 | 2100 | 0.727 | 3.6 | 124 | 131 | 1.65 |
35 | 33.0 | 25.7 | 1.6 | 2700 | 0.524 | 5.0 | 154 | 162 | 1.15 |
50 | 34.0 | 27.3 | 1.6 | 3100 | 0.387 | 7.1 | 187 | 197 | 0.87 |
70 | 38.0 | 30.3 | 2.0 | 4300 | 0.268 | 10.0 | 238 | 251 | 0.60 |
95 | 42.0 | 33.8 | 2.0 | 5400 | 0.193 | 13.6 | 289 | 304 | 0.45 |
120 | 47.0 | 37.8 | 2.5 | 6900 | 0.153 | 17.2 | 335 | 353 | 0.37 |
150 | 52.0 | 41.9 | 2.5 | 8200 | 0.124 | 21.4 | 386 | 406 | 0.30 |
185 | 57.0 | 46.7 | 2.5 | 10000 | 0.0991 | 26.5 | 441 | 463 | 0.26 |
240 | 62.0 | 52.2 | 2.5 | 12500 | 0.0754 | 34.3 | 520 | 546 | 0.21 |
300 | 68.0 | 57.3 | 2.5 | 15200 | 0.0601 | 42.9 | 599 | 628 | 0.185 |
400 | 76.0 | 64.2 | 3.15 | 19600 | 0.0470 | 57.2 | 673 | 728 | 0.165 |
Five Core | |||||||||
1.5 | 16.0 | 11.2 | 0.9 | 450 | 12.1 | 0.20 | 23 | 29 | 27 |
2.5 | 17.5 | 12.9 | 0.9 | 550 | 7.41 | 0.40 | 31 | 39 | 16 |
4 | 19.0 | 14.2 | 0.9 | 665 | 4.61 | 0.6 | 42 | 52 | 10 |
6 | 21.5 | 15.9 | 1.25 | 950 | 3.08 | 0.9 | 53 | 66 | 6.8 |
10 | 24.0 | 18.2 | 1.25 | 1250 | 1.83 | 1.4 | 73 | 90 | 4.0 |
16 | 27.0 | 20.3 | 1.6 | 1750 | 1.15 | 2.2 | 94 | 115 | 2.5 |
25 | 32.0 | 25.0 | 1.6 | 2450 | 0.73 | 3.6 | 124 | 152 | 1.7 |
35 | 36.0 | 28.4 | 1.6 | 3100 | 0.52 | 5.0 | 154 | 188 | 1.2 |
Nominal Cross Sectional Area (sqmm) | Approximate Overall Diameter (mm) | Approximate Diameter Under Armour (mm) | Nominal Diameter of Armour Wires (mm) | Approximate Cable Weight (kg/km) | Maximum Conductor Resistance at 20ºC (Ω/km) | Current Rating DC or Single Phase AC Clipped Direct (Amps) | Current Rating DC or Single Phase AC Free Air (Amps) | Volt Drop DC (mV/A/m) | Volt Drop Single Phase AC (mV/A/m) |
Two Core | |||||||||
1.5 | 13.0 | 8.6 | 0.9 | 320 | 12.1 | 27 | 29 | 31 | 31 |
2.5 | 14.0 | 9.9 | 0.9 | 380 | 7.41 | 36 | 39 | 19 | 19 |
4 | 15.0 | 10.8 | 0.9 | 445 | 4.61 | 49 | 52 | 12 | 12 |
6 | 16.5 | 12.1 | 0.9 | 540 | 3.08 | 62 | 66 | 7.9 | 7.9 |
10 | 19.0 | 14.3 | 0.9 | 720 | 1.83 | 85 | 90 | 4.7 | 4.7 |
16 | 21.0 | 15.6 | 0.9 | 990 | 1.15 | 110 | 115 | 2.9 | 2.9 |
25 | 25.0 | 18.9 | 1.25 | 1350 | 0.727 | 146 | 152 | 1.85 | 1.9 |
35 | 28.0 | 21.7 | 1.6 | 1900 | 0.524 | 180 | 188 | 1.35 | 1.35 |
50 | 28.0 | 21.3 | 1.6 | 1950 | 0.387 | 219 | 228 | 0.98 | 1.00 |
70 | 32.0 | 24.4 | 1.6 | 2450 | 0.268 | 279 | 291 | 0.67 | 0.69 |
95 | 33.0 | 25.3 | 2.0 | 3200 | 0.193 | 338 | 354 | 0.49 | 0.52 |
120 | 37.0 | 28.7 | 2.0 | 3800 | 0.153 | 392 | 410 | 0.39 | 0.42 |
150 | 39.0 | 31.2 | 2.0 | 4500 | 0.124 | 451 | 472 | 0.31 | 0.35 |
185 | 44.0 | 34.7 | 2.5 | 5800 | 0.0991 | 515 | 539 | 0.25 | 0.29 |
240 | 49.0 | 39.4 | 2.5 | 7100 | 0.0754 | 607 | 636 | 0.195 | 0.24 |
300 | 53.0 | 40.5 | 2.5 | 8600 | 0.0601 | 698 | 732 | 0.155 | 0.21 |
400 | 58.0 | 48.2 | 2.5 | 10500 | 0.0470 | 787 | 847 | 0.120 | 0.19 |
- No LPCB approval for 5 Core, BASEC approval for 1.5-10mm² inclusive
- Circular conductor 1.5 – 35sqmm. .
- Shaped conductor 50sqmm and above.
- Current ratings in accordance with BS 7671/IET Wiring Regulations.
- The tabulated ratings are based upon a 30°C ambient temperature and 90°C operating temperature.
- Minimum recommended installation temperature 0°C.
- Suitable for indoor and outdoor installations. Should be installed in accordance with BS 7671/IET Wiring Regulations or any other appropriate national regulations.
- Suitable for direct burial, trough, tray, ladder or other installations requiring a robust armoured cable.
FP Cable Accessories For Fire Resistant Cables
CABLE jOINTS ♦ CLEATS ♦ GLANDS
In order to protect the integrity of Prysmian FP fire resistant cables they should be installed in accordance with the manufacturers guidance including the use of fire resistant cable cleats, joints and glands.
View the complete range of Prysmian Cable Accessories for LV MV HV Cables, including 11kV-33kV networks or see product groups:
➡ For offshore cables, including BFOU and RFOU see Prysmian Draka.